Smart Sodium Hypochlorite System

Smart Sodium Hypochlorite System

Suitable for: Water Plant Disinfection Solutions (large equipment), Wastewater Plant Disinfection Solutions

Telephone:+86-13372145285 E-mail:jonzo@jonzo.cn

Technical Specifications

Item

Specification

Remarks

Available Chlorine Output

500 g/h – 50,000 g/h (customizable)

Covers needs from county/town water plants to large water plants

Electrode Material

Pure titanium substrate + Ru-Ir coating

Corrosion-resistant, long lifespan

Chlorine Concentration

5–8 g/L (sodium hypochlorite solution)

Ready to dose without dilution

Electrolytic Cell Type

Tubular / Plate bipolar electrolytic cell

Fewer connections, low power consumption

Salt / Power Consumption

Salt: 3.5 kg/kg; Power: 4.4 kW·h/kg

Industry-leading level

Power Supply

220V / 380V, power configured by model

Built-in rectifier power supply

Core Safety Features

Automatic hydrogen discharge, water softening system, anti-crystallization dosing

Ensures safe operation


Process Flow

Process Flow

Text Diagram Description

  • Water Softening — Removes water hardness, reduces scaling, automatic regeneration.
  • Salt Dissolving Tank — Dissolves food-grade salt into saturated brine.
  • Electrolyte Preparation — Dual closed-loop control for precise on-line preparation of 2–3% dilute brine.
  • Electrolytic Cell — Dilute brine enters the electrolytic cell and undergoes electrolysis under DC power.
  • Reaction — NaCl + H₂O → NaClO + H₂↑.
  • Storage & Dosing — The generated sodium hypochlorite solution is stored in a tank and precisely dosed to the disinfection point by metering pumps.
  • Hydrogen Discharge — By-product hydrogen is diluted to a safe concentration by a fan and discharged outdoors.

Installation Requirements

  • Site Requirements
    — Dedicated equipment room, good ventilation, level floor with drainage trench.
  • Environmental Requirements
    — Temperature 5°C–40°C, humidity <80%.
  • Utility Requirements
    — Nearby 220V/380V power supply, DN20–DN50 water inlet and drain outlet.
  • Safety Requirements
    — Hydrogen exhaust pipe must lead directly outdoors at a high point. Hydrogen alarm required in the equipment room.

Competitive Advantages

Comparison jonzo Smart Sodium Hypochlorite Generator Traditional Chemical Dosing / Standard Electrolysis Equipment
Raw Material & Safety Food-grade salt electrolysis, on-site generation, no hazardous chemical risk Purchased liquid chlorine or sodium hypochlorite — risks of transpo
Intelligence Fully automatic operation, AI predictive dosing algorithm, linked with water quality Mostly manual or timed dosing, delayed response
Operating Cost Low raw material cost High long-term chemical procurement costs
System Integration Standard water softening, automatic hydrogen discharge, IoT remote transmission Single function, requires additional supporting equipment

Related Solutions

Suitable for:

Water Plant Disinfection Solutions (large equipment), Wastewater Plant Disinfection Solutions

+86-13372145285
jonzo@jonzo.cn
Message